Hokkaido University Collection of Scholarly and Academic Papers >
Graduate School of Engineering / Faculty of Engineering >
Peer-reviewed Journal Articles, etc >
学校教室の窓ガラス仕様と空調条件が年間熱負荷に与える影響
Title: | 学校教室の窓ガラス仕様と空調条件が年間熱負荷に与える影響 |
Other Titles: | INFLUENCE OF THE WINDOW-GLASS SPECIFICATION AND AIR-CONDITIONING PRESET TEMPERATURE OF A SCHOOL CLASSROOM ONTO THE ANNUAL HEAT LOAD |
Authors: | 樋口, 作夫1 Browse this author | 羽山, 広文2 Browse this author →KAKEN DB | 絵内, 正道3 Browse this author →KAKEN DB |
Authors(alt): | Higuchi, Sakuo1 | Hayama, Hirofumi2 | Enai, Masamichi3 |
Keywords: | Classroom | Window-glass | U-value | Solar heat gain coefficient | Air-conditioning preset temperature | Taguchi method | 教室 | 窓ガラス | 熱貫流率 | 日射熱取得率 | 空調設定温度 | タグチメソッド |
Issue Date: | 30-Jul-2008 |
Publisher: | 日本建築学会 |
Journal Title: | 日本建築学会環境系論文集 |
Journal Title(alt): | Transactions of AIJ. Journal of environmental engineering |
Volume: | 73 |
Issue: | 629 |
Start Page: | 873 |
End Page: | 879 |
Publisher DOI: | 10.3130/aije.73.873 |
Abstract: | It is important to know how to balance the energy saving with the improvement of a learning environment in existing classrooms. This paper shows the influence of window glass specifications (area, U-value and Solar heat gain coefficient) and air-conditioning conditions (preset temperature for heating and cooling) onto the annual heat load of the school classroom. As a result of numerical calculations applying the Taguchi method, main points and effects to select the window glass and the air conditioning condition are shown as follows. 1) The influence of the preset temperature for heating is the largest in the area north than Osaka. 2) In the selection of glass performance in Sapporo, Morioka, Niigata, Osaka, and Fukuoka, U-value is more important for energy saving than the solar heat gain coefficient. 3) The influence of the window area is smallest in these 5 factors. 4) The low lapse rate of energy consumption would be expected from about 20 to 90% by the best selection of window glass and the air conditioning preset temperature setting. 5) An annual heat load presumed by Taguchi-method using SN ratio considering all 5 factors becomes smaller by about 30% than the load calculated by SMASH in the most suitable conditions. |
Rights: | 日本建築学会 |
Type: | article |
URI: | http://hdl.handle.net/2115/50461 |
Appears in Collections: | 工学院・工学研究院 (Graduate School of Engineering / Faculty of Engineering) > 雑誌発表論文等 (Peer-reviewed Journal Articles, etc)
|
Submitter: 羽山 広文
|