HUSCAP logo Hokkaido Univ. logo

Hokkaido University Collection of Scholarly and Academic Papers >
Graduate School of Engineering / Faculty of Engineering >
Peer-reviewed Journal Articles, etc >

流れの時間スケールを考慮した換気・通風空間のむらの評価指標とマクロモデルへの展開

Files in This Item:
AIJ.576.29-36.pdf1.25 MBPDFView/Open
Please use this identifier to cite or link to this item:http://hdl.handle.net/2115/50477

Title: 流れの時間スケールを考慮した換気・通風空間のむらの評価指標とマクロモデルへの展開
Other Titles: VOLUME INDEX TO EVALUATE THE SPACE WITH UNEVENNESS IN CONSIDERATION OF TIME SCALE AND DEVELOPMENT IN MARCO MODEL FOR CROSS VENTILATION
Authors: 西澤, 繁毅1 Browse this author
繪内, 正道2 Browse this author →KAKEN DB
羽山, 広文3 Browse this author →KAKEN DB
森, 太郎4 Browse this author →KAKEN DB
Authors(alt): Nishizawa, Shigeki1
Enai, Masamichi2
Hayama, Hirofumi3
Mori, Taro4
Keywords: Ventilation
Indoor air flow
Unevenness
Time scale
Volume index
Macro model analysis
換気
室内気流
むら
時間スケール
容積指標
マクロモデル解析
Issue Date: 28-Feb-2004
Publisher: 日本建築学会
Journal Title: 日本建築学会環境系論文集
Journal Title(alt): Transactions of AIJ. Journal of environmental engineering
Volume: 576
Start Page: 29
End Page: 36
Abstract: It's difficult to apply the age of air and ventilation effectiveness to evaluating the space with natural ventilation and cross ventilation, because the property of indoor environment changes under the influence of external condition. New index which expresses the unevenness in space for natural ventilation and cross ventilation is examined from movement and diffusion of tracer gas, in consideration of time scale of airflow field. And 2-zone model is examined as the macro model in consideration of unevenness. 1. Volume index is derived from concentration at exhaust to gas input at supply. And it is confirmed the index expresses the unevenness in space. 2. It is confirmed to able to grasp the overview of velocity distribution from the volume index. 3. 2-zone model based on the volume index is presented. And correspondence to the transient analysis is considered. 4. The identification method of the interzonal airflow rate is examined.
Rights: 日本建築学会、本文データは学協会の許諾に基づきCiNiiから複製したものである
Type: article
URI: http://hdl.handle.net/2115/50477
Appears in Collections:工学院・工学研究院 (Graduate School of Engineering / Faculty of Engineering) > 雑誌発表論文等 (Peer-reviewed Journal Articles, etc)

Submitter: 羽山 広文