Title: 室外機の吸込み温度の抑制手法である排気用ダクトに関する検討 : 多層階に設置される室外機の吸込み温度上昇に関する研究(続報)
Other Titles: EXHAUST DUCT FOR SUPPRESSION OF SUCTION TEMPERATURE OF OUTDOOR CONDENSING UNIT : Suction temperature characteristics of air-conditioner' outdoor condensing unit in multi-level installations (continued report)
Authors: 木下, 学1 Browse this author
羽山, 広文2 Browse this author →KAKEN DB
倉渕, 隆3 Browse this author →KAKEN DB
Authors(alt): Kishita, Manabu1
Hayama, Hirofumi2
Kurabuchi, Takashi3
Keywords: Outdoor condensing unit
Short-circuit air flow
Similarity rule
Modeling experiment
Exhaust duct
室外機
ショートサーキット流れ
相似則
模型実験
排気用ダクト
Issue Date: 30-Mar-2001
Publisher: 日本建築学会
Journal Title: 日本建築学会計画系論文集
Journal Title(alt): Transactions of AIJ. Journal of architecture, planning and environmental engineering
Volume: 541
Start Page: 31
End Page: 36
Abstract: The purpose of this report is to develop a scheme for optimal placement of outdoor condensing unit. With this purpose, we examine the relationship between rise in suction temperature and the placement of outdoor condensing unit in multi-level installations. In particular influence of exhaust duct is examined. A model experiment is performed for outdoor condensing. In addition, an equation for predicting rise in suction temperature for outdoor unit having an outside-air inflow rate R_m (ratio of outside-air inflow volume to air volume of the outdoor unit) is used to clarify the relationship between the rise in suction temperature of outdoor unit and equipment setup conditions. Based on these results, factors that will determine setup conditions considering the rise in suction temperature of outdoor unit are found and a method for suppressing rise in suction temperature is evaluated.
Rights: 日本建築学会、本文データは学協会の許諾に基づきCiNiiから複製したものである
Type: article
URI: http://hdl.handle.net/2115/50483
Appears in Collections:工学院・工学研究院 (Graduate School of Engineering / Faculty of Engineering) > 雑誌発表論文等 (Peer-reviewed Journal Articles, etc)