HUSCAP logo Hokkaido Univ. logo

Hokkaido University Collection of Scholarly and Academic Papers >
Graduate School of Engineering / Faculty of Engineering >
Peer-reviewed Journal Articles, etc >

空調機停止後の室温変化を考慮した空調設備の信頼性評価に関する研究

Files in This Item:
AIJ.507.71-78.pdf866.8 kBPDFView/Open
Please use this identifier to cite or link to this item:http://hdl.handle.net/2115/50485

Title: 空調機停止後の室温変化を考慮した空調設備の信頼性評価に関する研究
Other Titles: EVALUATING RELIABILITY OF AIR-CONDITIONING SYSTEM CONSIDERING TEMPERATURE CHANGE AFTER A SHUTDOWN IN AIR-CONDITIONING UNITS
Authors: 羽山, 広文1 Browse this author →KAKEN DB
大島, 一夫2 Browse this author
高草木, 明3 Browse this author
松島, 修4 Browse this author
Authors(alt): Hayama, Hirofumi1
Oshima, Kazuo2
Takakusagi, Akira3
Matushima, Osamu4
Keywords: Air-conditioning
Reliability
Redundancy design
Unavailability
空気調和
信頼性
冗長設計
不稼働率
Issue Date: 30-May-1998
Publisher: 日本建築学会
Journal Title: 日本建築学会計画系論文集
Journal Title(alt): Transactions of AIJ. Journal of architecture, planning and environmental engineering
Volume: 507
Start Page: 71
End Page: 78
Abstract: Room temperature in a high heat-generating machine room increases with time after a shutdown in air-conditioning units according to the heat capacity of devices installed in the same room and along the outside of the building. This paper reports on the following studies that examined simple and convenient methods for evaluating and improving the reliability of air-conditioning system. 1) A method is presented for determining the probability that room temperature will exceed allowed temperature after a shutdown in air-conditioning units. Using this method, a simple method is proposed for calculating the reliability of air-conditioning system. 2) Using this simple calculation method, simulations are performed to investigate a method for improving the reliability of air-conditioning facilities in a high heat-generating machine room. 3) Taking into account the fact that the cooling performance of air-conditioning equipment changes according to temperature conditions, it is shown that the number of necessary air-conditioning units can be reduced while maintaining the same level of reliability.
Rights: 日本建築学会、本文データは学協会の許諾に基づきCiNiiから複製したものである
Type: article
URI: http://hdl.handle.net/2115/50485
Appears in Collections:工学院・工学研究院 (Graduate School of Engineering / Faculty of Engineering) > 雑誌発表論文等 (Peer-reviewed Journal Articles, etc)

Submitter: 羽山 広文

Export metadata:

OAI-PMH ( junii2 , jpcoar_1.0 )

MathJax is now OFF:


 

 - Hokkaido University