Hokkaido University Collection of Scholarly and Academic Papers >
Graduate School of Engineering / Faculty of Engineering >
Peer-reviewed Journal Articles, etc >
床吹出し空調システムの高効率化
Title: | 床吹出し空調システムの高効率化 |
Other Titles: | HEIGHTENING THE EFFICIENCY OF UNDERFLOOR AIR=CONDITIONING SYSTEMS |
Authors: | 羽山, 広文1 Browse this author →KAKEN DB |
Authors(alt): | Hayama, Hirofumi1 |
Keywords: | Energy conservation | Underfloor air conditioning | Air flow system | Air flow distribution | 省エネルギー | 床吹出し空調 | 気流方式 | 風量分布 |
Issue Date: | 20-Mar-1996 |
Publisher: | 日本建築学会 |
Journal Title: | 日本建築学会技術報告集 : journal of architecture and building science |
Volume: | 2 |
Start Page: | 110 |
End Page: | 114 |
Abstract: | Consideration is given to the relationship between the supply and return air-flow distribution system, which uses the raised flooring and the ceiling as chambers, and energy consumption. The following four points are covered : 1) the definition of an index for evaluating the uniformity of the chambers' supply and return air-flow distribution ; 2) a proposed formula for estimating the relationship between the air-flow distribution non-uniformity rate and the chamber-aperture rates and loss of pressure ; 3) experiments using scale models to verify the accuracy of the calculation method ; and 4) clarification of how the air-flow distribution non-uniformity rate and the ventilation temperature-difference of the equipment in the room affect the energy consumption of the air-conditioning system. |
Rights: | 日本建築学会、本文データは学協会の許諾に基づきCiNiiから複製したものである |
Type: | article |
URI: | http://hdl.handle.net/2115/50507 |
Appears in Collections: | 工学院・工学研究院 (Graduate School of Engineering / Faculty of Engineering) > 雑誌発表論文等 (Peer-reviewed Journal Articles, etc)
|
Submitter: 羽山 広文
|