HUSCAP logo Hokkaido Univ. logo

Hokkaido University Collection of Scholarly and Academic Papers >
Graduate School of Engineering / Faculty of Engineering >
Peer-reviewed Journal Articles, etc >

データセンターの機器冷却特性と空調効率に関する研究

Files in This Item:
AIJ.640.721-728.pdf1.05 MBPDFView/Open
Please use this identifier to cite or link to this item:http://hdl.handle.net/2115/50459

Title: データセンターの機器冷却特性と空調効率に関する研究
Other Titles: A study on cooling characteristics of ICT equipment and cooling performance in a data center
Authors: 羽山, 広文1 Browse this author →KAKEN DB
降旗, 由紀2 Browse this author
森, 太郎3 Browse this author →KAKEN DB
絵内, 正道4 Browse this author →KAKEN DB
木下, 学5 Browse this author
Authors(alt): Hayama, Hirofumi1
Furihata, Yuki2
Mori, Taro3
Enai, Masamichi4
Kishita, Manabu5
Keywords: Air Conditioning
Data Center
Forced Air cooling
Ventilation Flow Amount
Energy Consunption
空気調和
データセンター
強制空冷方式
換気流量比
エネルギー消費
Issue Date: Jun-2009
Publisher: 日本建築学会
Journal Title: 日本建築学会環境系論文集
Journal Title(alt): Transactions of AIJ. Journal of environmental engineering
Volume: 74
Issue: 640
Start Page: 721
End Page: 728
Publisher DOI: 10.3130/aije.74.721
Abstract: In the work reported here, we investigated the items listed below to identify factors that affect the ICT machine air intake temperature, focusing on the effects of machine cooling characteristics on air conditioning efficiency. 1)We created a machine cooling model that relates the temperatures in different parts, derived the parameters that affect the machine air intake temperature, and analyzed the factors that govern the machine cooling characteristics. 2)To understand the factors that affect the air intake temperature of rackmounted machines that generate high heat, we conducted experiments on the relation of the machine mounting method and the air intake temperature for various amounts of air conditioning in-flow. 3)We presented a method for determining the amount of air conditioning inflow that takes machine cooling characteristics into account, and evaluated the effect of machines cooling characteristics on air conditioning efficiency.
Rights: 日本建築学会
Type: article
URI: http://hdl.handle.net/2115/50459
Appears in Collections:工学院・工学研究院 (Graduate School of Engineering / Faculty of Engineering) > 雑誌発表論文等 (Peer-reviewed Journal Articles, etc)

Submitter: 羽山 広文

Export metadata:

OAI-PMH ( junii2 , jpcoar_1.0 )

MathJax is now OFF:


 

 - Hokkaido University